Model |
4G-30.2-40P |
Horse power: |
30HP |
Cooling capacity: |
9.9-89KW |
Displacement: |
84.5CBM/h |
Voltage: |
Customize |
Refrigerant: |
R404a/R134a/R507a/R22 |
Temperature: |
-10℃– +10℃ |
Motor power |
22kw |
Unit Standard Configuration Table |
|
Spare Parts/Models |
|
Condenser(cooling Area) |
300㎡ |
Refrigerant Receiver |
√ |
Solenoid valve |
√ |
Oil Separator |
√ |
High/Low pressure meter Plate |
√ |
Pressure control switch |
√ |
Check valve |
√ |
Low pressure meter |
√ |
High pressure meter |
√ |
Copper Pipes |
√ |
Sight Glass |
√ |
Filter Drier |
√ |
Shock tube |
√ |
Accumulator |
√ |
Model |
Condensing temperature ℃ |
Cooling capacity Qo (Watt) power consumption Pe(KW) |
||||||||||||
Evaporation temperature ℃ |
||||||||||||||
|
12.5 |
10 |
7.5 |
5 |
0 |
-5 |
-10 |
-15 |
-20 |
-25 |
-30 |
|||
4G-30.2Y |
50 |
Q |
61500 |
55800 |
50500 |
45650 |
36950 |
29500 |
23200 |
17870 |
13430 |
|
|
|
|
P |
16.09 |
15.42 |
14.76 |
14.10 |
12.79 |
11.50 |
10.22 |
8.94 |
7.67 |
|
|
||
60 |
Q |
53700 |
48650 |
44000 |
39700 |
32000 |
25450 |
19890 |
15210 |
11300 |
|
|
||
|
P |
17.65 |
16.80 |
15.96 |
15.14 |
13.54 |
11.99 |
10.49 |
9.03 |
7.60 |
|
|
||
70 |
Q |
45900 |
41600 |
37600 |
33850 |
27200 |
21550 |
16720 |
12680 |
9320 |
|
|
||
|
P |
19.22 |
18.16 |
17.14 |
16.15 |
14.25 |
12.46 |
10.75 |
9.12 |
7.55 |
|
|
||
|
Cooling capacity Qo (Watt) power consumption Pe(KW) |
|||||||||||||
|
Evaporation temperature ℃ |
|||||||||||||
|
|
7.5 |
5 |
0 |
-5 |
-10 |
-15 |
-20 |
-25 |
-30 |
-35 |
-40 |
-45 |
|
30 |
Q |
103800 |
95300 |
79900 |
66500 |
54900 |
44900 |
36250 |
28800 |
224550 |
17040 |
12480 |
|
|
|
P |
19.21 |
19.07 |
18.57 |
17.81 |
16.84 |
15.70 |
14.41 |
13.02 |
11.57 |
10.09 |
8.61 |
|
|
40 |
Q |
89100 |
81800 |
68600 |
57000 |
47000 |
38250 |
30700 |
24200 |
18610 |
13860 |
9850 |
|
|
|
P |
23.37 |
22.88 |
21.73 |
20.38 |
18.88 |
17.26 |
15.56 |
13.81 |
12.06 |
10.33 |
8.68 |
|
|
50 |
Q |
74300 |
68200 |
57100 |
47400 |
38900 |
31500 |
25100 |
19580 |
14840 |
10810 |
7410 |
|
|
|
P |
27.01 |
26.20 |
24.46 |
22.58 |
20.60 |
18.56 |
16.50 |
14.45 |
12.45 |
10.54 |
8.76 |
Noted: Condensing unit without Refrigerant,When the unit is commissioned, the refrigerant is injected by professional technicians
Advantages
Advantages
Application
Product Structure
Product detail pictures:
Related Product Guide:
The company upholds the philosophy of "Be No.1 in quality, be rooted on credit and trustworthiness for growth", will continue to serve old and new customers from home and overseas whole-heatedly for Renewable Design for Condensing Unit Cold Room - 4G-30.2-40P 30HP CONDENSER UNIT – Cooler , The product will supply to all over the world, such as: Philippines, Eindhoven, Lyon, Our products have mainly exported to south-east Asia Euro-America, and sales to all of our country. And depending on excellent quality, reasonable price, best service, we have got good feedback from customers overseas. You are welcomed to join us for more possibilities and benefits. We welcome customers, business associations and friends from all parts of the world to contact us and seek cooperation for mutual benefits.
By Kimberley from Melbourne - 2018.12.25 12:43
We are a small company that has just started, but we get the company leader's attention and gave us a lot of help. Hope we can make progress together!
By Aurora from Cambodia - 2018.06.09 12:42